Clarke...the first name in fire protection.

LC2A Non-Listed Engine Series



Click an engine below to obtain specification data:

 

GROSS POWER RATINGS: AIR COOLED UNITS

Model

Guaranteed Speed RPM & Power kW (BHP) 

 

1760 

 1800

 2000

2100 

 2200

2350 

2400 

2600 

2800 

 2960

 3000

LC2A-NL30

11 

11 

13 

14

15 

15

16

16.5

17

19

19

 

14.5 

 15

 17

 18.5

 20 

 20.5

21 

22 

23

 25

25 

 

  • A 10% deduction must be made to the Gross Power Ratings in order to determine maximum engine power available for the maximum pump load (Gross Power / 1.1 = Maximum Pump Load).
  • All engines models will be provided with a nameplate indicating the Gross Power Rating and the Maximum Pump Load Power Rating.
  • All engine models and ratings shown are for Emergency, Stand-by Fire Protection use only.
  • Additional de-rates (as defined in NFPA 20) for ambient temperatures greater than 77°F (25°C) and for elevations above 300 feet (91m) shall be applied.

 

 