GROSS POWER RATINGS: AIR COOLED UNITS

 Model

 Guaranteed Speed RPM & Power kW (BHP)

 

1760 

 1800

 2000

2100 

 2200

2350 

2400 

2600 

2800 

 2960

 3000

LC3A-NL30 

15 

16

19

 19

19 

 21

22

 24

 25

26

26

 

20 

21

25

25

25

 28

29 

32

33 

35

35 


  • A 10% deduction must be made to the Gross Power Ratings in order to determine maximum engine power available for the maximum pump load (Gross Power / 1.1 = Maximum Pump Load).
  • All engines models will be provided with a nameplate indicating the Gross Power Rating and the Maximum Pump Load Power Rating.
  • All engine models and ratings shown are for Emergency, Stand-by Fire Protection use only.
  • Additional de-rates (as defined in NFPA 20) for ambient temperatures greater than 77°F (25°C) and for elevations above 300 feet (91m) shall be applied. 




     